Description:
The DR-60 is a commonly used rail-mounted switch mode power supply, extensively applied in fields such as industrial automation, electrical control cabinets, LED lighting, and security surveillance. Below is a general introduction and overview of its features:
Universal AC input/Full range
Protections:Short circuit/Overload/Over voltage
Cooling by free air convection
Can be installed on DIN RAIL TS-35/7.5 or 15
LED indicator for power on
No load power consumption<0.75W
100% full load burn-in test
2 years warranty
Industrial Automation: Powers PLCs, sensors, actuators, and other control components.
LED Lighting: Supplies stable power to small to medium-sized LED lighting fixtures.
Security Surveillance: Powers CCTV cameras, access control systems, and other security equipment.
Communication Equipment: Suitable for small-scale switches, routers, and the like.
Instrumentation: Provides power support for various measuring and testing equipment.
Specifications:
Model | DR-60-12 | DR-60-24 | DR-60-48 | |
Output | DC Voltage | 12V | 24V | 48V |
Current Range | 0-5A | 0-2.5A | 0-1.25A | |
Rated Power | 60W | 60W | 60W | |
Ripple Noise(Max) | 80mVp-p | 100mVp-p | 120mVp-p | |
Voltage Adj.Range | 12-15V | 24-30V | 48-55V | |
Voltage Tolerance | ±1.5% | ±1.0% | ±1.0% | |
Line Regulation | ±0.5% | ±0.5% | ±0.5% | |
Load Regulation | ±1.5% | ±1.0% | ±1.0% | |
Set up,Rise time | 500ms,30ms/230VAC 1000ms,30ms/115VAC(full load) | |||
Hold up Time | 60ms/230VAC 12ms/115VAC(full load) | |||
Input | Voltage Range | 85 ~264VAC 120~370VDC | ||
Frequency | 47 ~ 63Hz | |||
Efficiency | 77% | 81% | 83% | |
AC Current | 0.55A/115VAC 4A/230VAC | |||
Inrush Curent | 40A/230VAC | |||
Leakage Current | <1mA / 240VAC | |||
Protection | Overload | 105 ~ 130% rated output power | ||
Protection tye:Constant current limiting,recovers automatically after fault condition is removed | ||||
Over Voltage | 14-17V | 29-33V | 56-65V | |
Protection type : Shut off o/p voltage, re-power on to recover | ||||
Environment | Working Temperature | -10~ +60℃ (Refer to derating curve as datasheet from SMUN) | ||
Working Humidity | 20 ~ 90% RH non-condensing | |||
Storage Temp.Humidity | -20 ~ +85℃, 10 ~ 95% RH | |||
Temp.Coefficient | ±0.03%/℃ (0 ~ 50℃) | |||
Vibration | Component:10~500Hz,2G 10min./1 cycle,60min. each along X,Y,Z axes | |||
Safety | Safety Standards | CE and GB4943.1 Safety standard | ||
Withstand Voltage | I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |||
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC/25℃/70% RH | |||
EMC Emission | Compliance to EN61000-3-2:2014/EN61000-3-3:2013 | |||
EMC Immunity | Compliance to EN55032:2015/EN55035:2017/60950-1 | |||
Others | MTBF | ≥327.9K hrs MIL-HDBK-217F(25℃) | ||
Dimension | 93*78*56mm (L*W*H) | |||
Packing | 0.25Kg; 60pcs/15Kg | |||
Note | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line ragulation and load regulation. 4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.In case the adjacent device is a heat soure, 15mm clearance is recommended 6. Derating may be needed under low input voltage. Please check the derating curve for more details. 7.Please contact with SMUN customer service for more details. |