Description:
The MDR-20 is a slim-profile DIN rail-mounted switch mode power supply designed for applications in industrial automation, instrumentation, LED lighting, security systems, and any other scenarios requiring a stable DC power source. Renowned for its compact dimensions, high efficiency, and reliability, the MDR-20 offers a range of features tailored to demanding environments.
Universal AC Input: Compatible with a wide range of AC input voltages, typically ranging from 85VAC to 264VAC, making it suitable for global use across diverse electrical grids.
DIN Rail Mounting: Conforms to standard DIN TS35/7.5 or TS35/15 rail mounting, facilitating quick installation and ease of maintenance.
Ultra-Slim Design: Specifically engineered with a thin profile to fit into space-constrained installations.
Output Specifications: The MDR-20 series provides various output voltage options such as 5V, 12V, 15V, 24V, among others, with an output power capacity around 20W. For example, the MDR-20-12 delivers 12V DC at 1.67A, while the MDR-20-24 supplies 24V DC at 0.83A.
Protection Functions: Equipped with overload, short circuit, and overvoltage protection mechanisms to ensure both the power supply's and connected devices' safety, complemented by a DC OK indicator for status monitoring.
Low Standby Power Consumption: Optimized for low power draw when idle, contributing to energy savings.
Industrial Control: Powers PLCs (Programmable Logic Controllers), sensors, actuators, and more.
Instrumentation: Suitable for powering various measurement and monitoring instruments.
LED Lighting: Ideal as a driver for LED lighting systems.
Security Systems: Provides power for CCTV cameras, access control systems, etc.
Communication Equipment: Supports small-scale switches, routers, and similar equipment.
Specifications:
Model | MDR-20-12 | MDR-20-24 | MDR-20-48 | |
Output | DC Voltage | 12V | 24V | 48V |
Current Range | 0-1.67A | 0-1A | 0-0.4A | |
Rated Power | 20W | 24W | 19.2W | |
Ripple Noise(Max) | 120mVp-p | 150mVp-p | 180mVp-p | |
Voltage Adj.Range | 10.8~13.2V | 21.6~26.4V | 43.2~52.8V | |
Voltage Tolerance | ±1.0% | ±1.0% | ±1.0% | |
Line Regulation | ±1.0% | ±1.0% | ±0.2% | |
Load Regulation | ±1.0% | ±1.0% | ±0.5% | |
Set up,Rise time | 500ms,30ms/230VAC 1000ms,30ms/115VAC(full load) | |||
Hold up Time | 50ms/230VAC 20ms/115VAC(full load) | |||
Input | Voltage Range | 85 ~264VAC 124~370VDC | ||
Frequency | 47 ~ 63Hz | |||
Efficiency | 80% | 80% | 84% | |
AC Current | 0.55A/115VAC 0.35A/230VAC | |||
Inrush Curent | 20A/115VAC 40A/230VAC | |||
Leakage Current | <1mA / 240VAC | |||
Protection | Overload | 105~160 rated output power | ||
Protection type:hiccup mode,recovers automatically after faul condition is removed. | ||||
Over Voltage | 13.8~16.2V | 28.5~33.8V | 41.4~48.6V | |
Protection type : Shut down o/p voltahe, recovers automatically after fault condition is removed | ||||
Function | DC OK Active Signal(Max.) | 9~13.5V/40mA | 18~27V/20mA | 41~54V/10mA |
Environment | Working Temperature | -20~ +70℃ (Refer to derating curve as datasheet from SMUN) | ||
Working Humidity | 20 ~ 90% RH non-condensing | |||
Storage Temp.Humidity | -20 ~ +85℃, 10 ~ 90% RH | |||
Temp.Coefficient | ±0.03%/℃ (0 ~ 50℃) | |||
Vibration | Component:10~500Hz,2G 10min./1 cycle,60min. each along X,Y,Z axes; Mounting: Compliance IEC60068-2-6 | |||
Safety | Safety Standards | Comply with CE and GB4943.1 safety standards | ||
Withstand Voltage | I/P-O/P:2KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC/25℃/70% RH | |||
EMC Emission | EN61000-3-2:2014/EN61000-3-3:2013 | |||
EMC Immunity | EN55032:2015/EN55035:2017/60950-1 | |||
Others | MTBF | 236.9k hrs MIL-HDBK-217F(25℃) | ||
Dimension | 22.5*90*100mm (L*W*H) | |||
Packing | 0.19Kg; 72pcs/14.7Kg/0.91CUFT | |||
Note | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The output needs to be reduced under the condition of low input voltage, refer to the derating curve chart for details. 5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may increase of the set up time. 6.Please contact with SMUN customer service for more details. |
Home About Us Power Supply Service&Support Solution Blogs Contact Us Privacy Policy