Description:
The SDR-240 series is a DIN rail-mounted switch power supply,is widely used in industrial control, automation equipment, instrumentation, communication devices, and LED lighting applications, among others. Here is an overview of its key features and specifications:
Wide Range Input Voltage: The SDR-240 series is designed with a wide input voltage range, typically covering 85-264VAC or 100-370VDC, enabling it to operate stably across various global electrical standards, thereby enhancing its versatility and flexibility.
High Efficiency: As an energy-efficient power supply, the SDR-240 typically achieves conversion efficiency above 80%, with some models even higher. This not only reduces energy consumption but also lowers operating costs and environmental impact.
Low No-Load Power Consumption: In compliance with standards like ErP Lot 6, these power supplies have minimal power draw when unloaded or lightly loaded, aligning with green energy-saving requirements.
Comprehensive Protection Mechanisms: Beyond basic protections such as Short Circuit Protection (SCP), Overvoltage Protection (OVP), and Overload Protection (OLP), the SDR-240 may also feature Over-Temperature Protection (OTP), ensuring automatic output cutoff under abnormal conditions to prevent damage.
International Certifications: These products typically pass multiple international safety certifications, including CE, TÜV, among others, assuring product quality and safety for global market applications.
Adjustable Output Voltage: Some models might offer output voltage fine-tuning, allowing users to adjust the voltage output according to specific needs, increasing flexibility.
Industrial Automation: Provides stable DC power for PLC controls, sensors, actuators, and other industrial automation equipment.
Security & Surveillance: Powers CCTV cameras, access control systems, alarm systems, and other security devices, ensuring 24/7 uninterrupted operation.
LED Lighting: Suitable for indoor and outdoor LED lighting systems, particularly for LED strips and fixtures requiring constant voltage drive.
Telecommunication Equipment: Supplies power to routers, switches, wireless access points, and other telecommunications infrastructure, ensuring data transmission stability.
Instrumentation & Control Systems: Used in various measuring instruments, automation control systems, providing power for controllers, displays, etc.
Medical Devices: While not all SDR-240 models are suitable for medical devices, certain certified models can be used for auxiliary power in medical instruments such as monitoring devices and small-scale therapy equipment.
Specifications:
Model | SDR-240-12 | SDR-240-24 | SDR-240-48 | |
Output | DC Voltage | 12V | 24V | 48V |
Current Range | 0-20A | 0-10A | 0-5A | |
Rated Power | 240W | 240W | 240W | |
Ripple Noise(Max) | 100mVp-p | 120mVp-p | 150mVp-p | |
Voltage Adj.Range | 12-14V | 24-28V | 48-55V | |
Voltage Tolerance | ±1.0% | ±1.0% | ±1.0% | |
Line Regulation | ±0.5% | ±0.5% | ±0.5% | |
Load Regulation | ±1.0% | ±1.0% | ±1.0% | |
Set up,Rise time | 1500ms,60ms/230VAC 3000ms,60ms/115VAC(full load) | |||
Hold up Time | 20ms/230VAC 20ms/115VAC(full load) | |||
Input | Voltage Range | 88 ~264VAC 124~370VDC[DC input operation possible by connecting AC/L(+),AC/N(-)] | ||
Frequency | 47 ~ 63Hz | |||
Efficiency | 85% | 88% | 90% | |
AC Current | 1.4A/115VAC 0.85A/230VAC | |||
Inrush Curent | 30A/115VAC 50A/230VAC | |||
Leakage Current | <1mA / 240VAC | |||
Protection | Overload | Normally works within 110~150% rated output power for more than 3 seconds and then shut down o/p voltage,re-power on to recover | ||
150~170%rated power,constant current limiting with auto-recovery within 3 seconds,and then shut down o/p voltage after 3 seconds,re-power on to recover | ||||
Over Voltage | 14-17V | 29-33V | 56-65V | |
Protection type : Shut down o/p voltahe, re-power on to recover | ||||
Over Temperature | Shut down o/p voltage,re-power on to receover after temperature goes down | |||
Environment | Working Temperature | -30~ +70℃ (Refer to derating curve as datasheet from SMUN) | ||
Working Humidity | 20 ~ 95% RH non-condensing | |||
Storage Temp.Humidity | -40 ~ +85℃, 10 ~ 95% RH | |||
Temp.Coefficient | ±0.03%/℃ (0 ~ 50℃) | |||
Vibration | Component:10~500Hz,2G 10min./1 cycle,60min. each along X,Y,Z axes; Mounting: Compliance IEC60068-2-6 | |||
Safety | Safety Standards | Ul508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet BS EN/EN60204-1) | ||
Withstand Voltage | I/P-O/P:2KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC/25℃/70% RH | |||
EMC Emission | Compliance to BS EN/EN55032(CISPR32), BS EN/EN61000-3-2,EAC TP TC 020, CNS13438 Class A | |||
EMC Immunity | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11,BS EN/EN55024, BS EN/EN61000-6-2(BS EN/EN50082-2), heavy industry level, criteria A,EAC TP TC 020 | |||
Others | MTBF | 292.1k hrs MIL-HDBK-217F(25℃) | ||
Dimension | 63*125.2*113.5mm (L*W*H) | |||
Packing | 1.03Kg; 12pcs/13.4Kg/1.22CUFT | |||
Note | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line ragulation and load regulation. 4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.In case the adjacent device is a heat soure, 15mm clearance is recommended 6. Derating may be needed under low input voltage. Please check the derating curve for more details. 7.Please contact with SMUN customer service for more details. |